What is a Flameless Explosion Venting Device?

2025-09-19

Flameless explosion venting devices are core components of modern industrial explosion protection systems, equivalent to installing an "intelligent safety valve" for equipment. When a dust or gas explosion occurs, they can complete three actions—pressure relief, flame suppression, and temperature reduction—within milliseconds.


How does a flameless explosion venting device work?
Principle of operation

When an explosion occurs, the rupture plate opens, and when the flame passes through the mesh flame arresting element, the flame arresting element exchanges heat with the flame, rapidly cools down the high temperature flame, releases pressure and smoke, ensures that the flame is not propagated to avoid causing a secondary explosion or multiple explosions, and at the same time, the pressure wave or noise generated by the explosion will be reduced to a lower level.


What are the different types of flameless explosion venting device?
We offer a variety of flameless venting structures to meet different operational needs, such as circular, rectangular, and square designs.

Material: Carbon Steel Housing + Stainless Steel Filter

Flameless relief device requires no special maintenance

Flange connection can be customized


What are the usage and maintenance requirements for flameless explosion venting devices?


Use and Maintenance

The flameless relief device is a passive, mechanical principle of action and requires no commissioning after installation.
It is recommended that the safety zone be defined according to the diagram below to ensure that no additional injuries are caused in the event of a dust explosion. Where: d1 > 1m (for equipment buildings); d2 > 2.5m (for personnel).
Regularly inspect the surface of the flameless relief device for accumulation of dust, snow, ice, or the presence of other buildup that interferes with the proper functioning of the relief device, and if so, remove it by appropriate means.
Regularly inspect the pressure relief element (bursting plate) for breakage, the inspection period should be no more than 1 month.
Regularly check the fire extinguishing element for blockage, the inspection period should be no more than 1 week.
If the pressure relief element is found to be broken, it should be shut down and replaced in time. During the replacement process, it should be ensured that there is no residual dust or effective ignition source.
If there is an optional alarm output, please check the wiring regularly for any abnormality, and the inspection cycle is recommended to be no more than 1 week.
If the flameless relief device is found to be leaking powder or air, the rupture plate may have burst due to overpressure, which can be initially checked through the inspection port.
If there is an optional alarm output, when there is a signal display on the alarm output, it means that the bursting board is ruptured and the replacement of the bursting board is required.
When the dust explosion, the flameless relief device releases smoke and accompanied by sound, if this happens, please stop the machine immediately to check.

After the dust explosion, please do not touch the flameless relief device to avoid burns.


Our R&D center laboratory and testing base cover an area of over 7,000 square meters, making it the largest comprehensive safety pressure relief R&D testing institution in China, and the only organization in the country with the capability and qualifications to conduct full-range testing of key metrics for safety pressure relief equipment.