·lt is the first in the world to install the detection sensing device directly on the detection surface without the need for a
light guide column,and never let go of any potential safety hazards.
·Adopt 304 stainless steel pilot solenoid valve and 304 stainless steel high-pressure nozzle and obtain invention patent.
·Intelligent control of the electrical box,record all on-off time and spark occurrence time and extinguishing time.
·The extra low water pressure alarm signal device for pressurized water ensures the safety of high-pressure water supply
in real time.
·Anti-jamming hub box,which can filter external power interference and noise interference.
Installation and arrangement
The distance of the spark detector from the nearest branch pipe should be >1.3m.
·Distance from spray extinguishing device to spark detector >8.5m.
·The distance of the spray extinguishing device from the downstream pipe elbow is more than1.8m,that is,the distance of
the pipe diameter*2.
·Do not install the spark detector on the pipe elbow,but on the straight pipe part.
·Spark Detector Arrangement:Two spark detectors are arranged face to face horizontally on the same cross section of
the pipeline,Keep in mind that it is not allowed to be placed at the bottom of the pipe.
·Use the special tool that comes with the goods to punch a hole in the pipe and install it without entering the inside of the
pipe.
Use the special tool supplied with the shipment to make a hole in the pipe for installation without going inside the pipe.